PubMed HealthSearch

PubMed · 8011060

[Ventilation method plan in daily operations--a practical study].

Abstract

On three days each we measured particles and airborne bacteria in ten ventilated operating theatres. Modern air conditioning systems achieved a significant reduction of air-pollution. Vertical systems proved to be more effective than horizontal systems. Workday conditions made several problems: During high personal activity a body exhaust system was not able to reduce the concentration of airborne bacteria; doors near the operating table and objects in the airstream had a negative effect; there was more personal than necessary in the operating theatres; some activities took place without a specific purpose and resulted in raised particle and bacteria contamination; early clearing of materials, before the operation ended, increased turbulences and door movements. A short break in personal activity before the first skin cut is recommended to reduce high air contamination due to the preparation of the operating room and the patient. One of the ventilation systems was insufficiently operated by personal. We recommend continuous measurement of particles near the operating field in order to control the input of airborne particles and bacteria into the wound.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

W E Bischoff, U Sander, J Sander. 1994. [Ventilation method plan in daily operations--a practical study].. https://pubmed.ncbi.nlm.nih.gov/8011060/

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related citations

Evaporative cooling and other home factors and lower respiratory tract illness during the first year of life. Group Health Medical Associates.

Lower respiratory tract illness (LRI) is associated with exposure to various environmental factors. The relation between home environment and LRI in infants was studied with the use of data from the Children's Respiratory Study in Tucson, Arizona. Healthy infants from a health maintenance organization were recruited at birth (1980-1984). Analysis was restricted to one infant per family, and to those followed through the first year (n=936). Environmental data were collected at enrollment, and clinicians diagnosed LRI according to predetermined criteria. During the first year of life, 196 infants (21%) had wheezing LRI, and 60 (6%) had nonwheezing LRI. The risk of wheezing LRI was higher in infants with evaporative home cooling (24%) than in those without evaporative home cooling (15%) (odds ratio = 1.8, 95% confidence interval 1.1-3.0); this association was stronger among infants who lived with other children in the home. The risk of nonwheezing LRI was associated with parents' rating of neighborhood dustiness, ranging from 5% in the least dusty environments to 12% in the dustiest (p for trend = 0.002). Neither association could be explained by confounding factors. LRI was not related to the type of home heating, cooking fuel, or the numbers of indoor dogs or cats.

Air Conditioning

Field trial of biocides for control of Legionella in cooling towers.

Legionella and amebae populations in 16 cooling towers were challenged with three commercially available biocide formulations. The active agents were: a chlorinated phenolic thioether (CPTE), bromo-nitro-propane-diol (BNPD), and bromo-chloro-dimethylhydantoin (BCD, in briquette form). The towers were dosed with these biocides for approximately 4 weeks. BCD was effective against Legionella in each of nine challenge experiments, and CPTE in eight of nine challenges. BNPD was effective in only five of 11 challenges. None of the biocides had any significant effect in reducing planktonic amebae concentrations during the challenges.

Air Conditioning